Monitored PDU - PDB-191-V 16

Description
PDU - Details / Function:
1. Casing: Sheet metal / black
2. LCD display on the device and monitoring via the console:
Monitoring of total load current,
total voltage, total power, total energy,
power factor, load current of each individual unit, and
On/Off status of each individual unit.
3. Support:
TCP/IP, SNMP V1/V2C/V3, Http/Https, IPV4/IPV6, SMTP, MODBUS
4. Upstream fuse: Schneider FI-A 20A-2P (= Type A version)
5. Output fuse for the output sockets: Chint, NXB-C16A/2P
6. Vertical installation
Explanation:
RCD protection is very important for people, which is why we equip the PDU with a 30 mA Type A RCD as standard. When it comes to a UPS, it is important to keep direct currents in mind, as a Type A is not suitable for this; you would need a Type B circuit breaker. Therefore, we offer you two selection options. We recommend only the Type B version when used with a UPS!
Technical Data
Specifications
| Type | Basic PDB-191 |
|---|---|
| Input | 230VAC - 16A |
| Output | 230VAC |
| Output variant 1 | 3x Schuko 16A |
| Output variant 2 | 3x IEC save 16A |
| Output variant 3 | 3x CEE blue 16A |
| Expansion | Cascade up to 9 units, all in monitoring |
| Dimensions | L 1130 mm x D 90 mm x W 155 mm |
PDU - Details / Function:
1. Casing: Sheet metal / black
2. LCD display on the device and monitoring via the console:
Monitoring of total load current,
total voltage, total power, total energy,
power factor, load current of each individual unit, and
On/Off status of each individual unit.
3. Support:
TCP/IP, SNMP V1/V2C/V3, Http/Https, IPV4/IPV6, SMTP, MODBUS
4. Upstream fuse: Schneider FI-A 20A-2P (= Type A version)
5. Output fuse for the output sockets: Chint, NXB-C16A/2P
6. Vertical installation
Explanation:
RCD protection is very important for people, which is why we equip the PDU with a 30 mA Type A RCD as standard. When it comes to a UPS, it is important to keep direct currents in mind, as a Type A is not suitable for this; you would need a Type B circuit breaker. Therefore, we offer you two selection options. We recommend only the Type B version when used with a UPS!
Specifications
| Type | Basic PDB-191 |
|---|---|
| Input | 230VAC - 16A |
| Output | 230VAC |
| Output variant 1 | 3x Schuko 16A |
| Output variant 2 | 3x IEC save 16A |
| Output variant 3 | 3x CEE blue 16A |
| Expansion | Cascade up to 9 units, all in monitoring |
| Dimensions | L 1130 mm x D 90 mm x W 155 mm |