Monitored PDU - PDB-193-V 16

Description
PDU - Details / Function:
1. Enclosure: Sheet metal / black
2. LCD display on the device and monitoring via the console:
Monitoring of total load current,
total voltage, total power, total energy,
power factor, load current of each individual unit, and
on/off status of each individual unit.
3. Support:
TCP/IP, SNMP V1/V2C/V3, Http/Https, IPV4/IPV6, SMTP, MODBUS
4. Upstream fuse: Schneider RCD 30 mA - 20A - 4P (= Type A version)
5. Output fuse of the outlets: Chint, NXB-C16A/2P
6. Outlets: 9x Schuko (3x Schuko per phase)
7. 16A IP44 industrial plug (plug + socket, 5-pin, 6h)
8. Vertical installation (19" mounting brackets can be rotated)
Explanation:
RCD protection is very important for people, which is why we equip the PDU with a Type A 30 mA RCD as standard. When it comes to a UPS, it is important to keep an eye on DC currents, because a Type A is not suitable for this; you need a Type B circuit breaker. Therefore, we offer you two selection options. We recommend using only the Type B variant with a UPS!
Technical Data
Specifications
| Type | Basic PDB-193-V |
|---|---|
| Input | 230/400VAC - 16A (3-phase) |
| Output | 230VAC - 9x Schuko |
| Extension | Cascade up to 9 units, all monitored |
| Dimensions | L 1500 mm x D 90 mm x W 155 mm |
PDU - Details / Function:
1. Enclosure: Sheet metal / black
2. LCD display on the device and monitoring via the console:
Monitoring of total load current,
total voltage, total power, total energy,
power factor, load current of each individual unit, and
on/off status of each individual unit.
3. Support:
TCP/IP, SNMP V1/V2C/V3, Http/Https, IPV4/IPV6, SMTP, MODBUS
4. Upstream fuse: Schneider RCD 30 mA - 20A - 4P (= Type A version)
5. Output fuse of the outlets: Chint, NXB-C16A/2P
6. Outlets: 9x Schuko (3x Schuko per phase)
7. 16A IP44 industrial plug (plug + socket, 5-pin, 6h)
8. Vertical installation (19" mounting brackets can be rotated)
Explanation:
RCD protection is very important for people, which is why we equip the PDU with a Type A 30 mA RCD as standard. When it comes to a UPS, it is important to keep an eye on DC currents, because a Type A is not suitable for this; you need a Type B circuit breaker. Therefore, we offer you two selection options. We recommend using only the Type B variant with a UPS!
Specifications
| Type | Basic PDB-193-V |
|---|---|
| Input | 230/400VAC - 16A (3-phase) |
| Output | 230VAC - 9x Schuko |
| Extension | Cascade up to 9 units, all monitored |
| Dimensions | L 1500 mm x D 90 mm x W 155 mm |